Authored by Faizal Afzal
The Mitsubishi FR-E700 series Variable Frequency Drive (VFD), particularly the FR-E720 model, is renowned globally for its compact size, high quality, and cost-effectiveness. This makes it a popular choice for various industrial applications. In this guide, we will explore how to use the Siemens S7-1200 PLC, combined with the CB 1241 RS485 module, to control the FR-E720 inverter via Modbus-RTU communication.
This tutorial provides a detailed, step-by-step approach, from wiring connections to parameter configurations, ensuring you have all the necessary information to implement this setup effectively.
Before beginning the configuration, it is essential to establish the correct wiring connections between the Siemens S7-1200 PLC and the Mitsubishi FR-E720 VFD. The S7-1200 PLC uses the CB 1241 RS485 module for communication, which interfaces with the FR-E720’s Modbus-RTU communication port.
S7-1200 & FR-E720 Wiring Diagram
Key Wiring Points:
For the FR-E720 to communicate effectively via Modbus-RTU, certain parameters must be configured. Below is a list of essential parameters that need to be set on the FR-E720 inverter.
FR-E720 Modbus-RTU Communication Parameters:
FR-E720 Parameter Configuration Table
These settings ensure that the FR-E720 VFD is correctly configured to communicate via Modbus-RTU, allowing the Siemens S7-1200 PLC to send and receive data.
The FR-E720 VFD uses specific Modbus register addresses to control and monitor its operations. Below are the key register addresses required for basic control functions.
Modbus Register Addresses:
Control Commands:
Modbus Register Address Table
These register addresses and commands are fundamental for controlling the VFD’s operation, such as starting, stopping, and changing the direction of the motor.
For monitoring purposes, the Siemens S7-1200 PLC can read data from the FR-E720 VFD using Modbus registers. In this example, we will read three consecutive registers that contain essential operational data.
Monitoring Register Addresses:
Data Output Monitoring Configuration
This configuration allows the PLC to monitor critical parameters such as output frequency, current, and other operational metrics from the VFD.
To establish communication between the Siemens S7-1200 PLC and the FR-E720 VFD, the CB1241 RS485 module must be configured correctly. This section outlines the necessary steps for configuring the module and building the Modbus communication blocks.
Steps for Configuration:
Siemens S7-1200 PLC Configuration
Siemens S7-1200 PLC Configuration
Proper configuration of the PLC and RS485 module ensures seamless communication with the VFD, allowing for effective control and monitoring.
The final step involves programming the Siemens S7-1200 PLC to control the FR-E720 VFD. Below are the key programming elements required for successful VFD control.
Programming Steps:
These programming steps are essential for integrating the VFD control into your automation system, ensuring that the motor operates as required.
This comprehensive guide has walked you through the entire process of configuring and programming the Siemens S7-1200 PLC to control the Mitsubishi FR-E720 VFD via Modbus-RTU. By following these steps, you can achieve reliable and efficient control of the FR-E720, leveraging the power of Siemens automation technology in your industrial applications.
With this setup, you can easily integrate the FR-E720 VFD into a wide range of automation systems, ensuring optimal performance and control.

Smart Asset Tracking & Monitoring Solution for Process...

Smart Utility Management Solution Smart Utility Management...

Revolutionizing with Mobile Solutions Over the past decade,...

Maximizing Manufacturing Productivity with OEE Understanding...

Real-Time Data Analysis Unlike traditional preventive...

Optimizing Industrial Alarm Management: Enhancing Plant...

Condition-Based Maintenance (CbM) Optimizing Maintenance for...